The performance of TP600-2U of inverter is at top of the market with peak efficiency up to 90% and small harmonics on DC side and it can be interfaced with RS232 and RS485.
- Dry Contact Outputs: The equipment must have dry contact outputs to report the basic alarms. You must have at least three dry contacts that report: No DC voltage at the input; No AC voltage at the input;
This is our popular one subrack inverter, we have more than 5000units sales every year.
Here are the Features;
- 19”1U or 19”2U
- High Frequency standby design with
- Transfer time 5-8ms
- Working mode selectable (AC priority or DC priority)
- High Frequency design
- DC/AC isolation improving system security
- System parameters programmable
- Complete protection
- Thermal controlled fan
- RS232 or RS485 communication port and Dry point
- Voltage adjustable 230Vac (200-240) or 110Vac (100-120)
- Front panel connection version available
LED shows
LED/Button | Symbol | Qty | Color | Status |
Silence | Silence button | 1 | Press continually for 1sec to turn ON INAUDIBLE | |
Mode | AC mode | 1 | Green | It illuminates when the mode is on AC mode |
Bypass | AC Bypass | 1 | Green | It illuminates when unit is on bypass mode |
Inverter | Inverter on | 1 | Green | It illuminates when inverter is normal operation |
Fault | Fault | 1 | Red | It is on in case of INVERTER faulty |
Battery capacity | 4 | Green | ≤25%,≤50%,≤75%,≤100% | |
Load level | Load | 4 | Green | ≤25%,≤50%,≤75%,≤100% |
DC low | 1 | Yellow | It illuminates when DC voltage is lower than limit | |
Overload | 1 | Yellow | It illuminates when load > 100% |
Structure
Specifications
TP600D and TP600E (110VDC/220VDC models)
Model | TP610 / TP620 / TP630 | TP640 / TP650 / TP660* |
Electrical | ||
DC Input | 110Vdc/ 125Vdc/220Vdc | |
DC Input | 110V/220V:-17%~+25%,125V:-20% ~+15% | |
AC input | 230Vac or 110Vac (-25%~+20%) | 230Vac (-25%~+20%) |
Frequency range | ±10% | |
Contious Power (40℃) | 1Kva - 6Kva | |
Power factor | 0.8 | 0.7 |
Nominal output voltage | 230Vac or 110Vac | 230Vac |
Voltage variation | Max ± 2% | |
Output frequency | 50/60Hz ± 0.1Hz | |
Efficiency | Max 90% | |
THD | <3% liner load | |
<5% non-liner load | ||
Crest factor | .3:1 | |
Overload | 125% 60secs (TP660 10secs) | |
110% 10mins (TP660 30secs) | ||
Transfer time | 5-8ms | |
Dynamic response time | < 30ms | |
LVD | 91.5,104Vdc or 183Vdc | |
Display & Communication | ||
Communication Interface | RS232 and RS485 | |
4xDry contact | ||
Safety & Environment | ||
Operating Temp. | Full load, <-20℃> - 40℃ | |
Derating using, 40℃ - 60℃ | ||
Isolation | 2000Vrms | |
Mechanical | ||
Dimension (WxH) | 19"2U | |
Depth | 256mm / 321mm | 321mm |
Weight | 6kgs / 12kgs | 12kgs |
Cooling | forced fan with thermal control | |
Enclosure | IP20 | |
Standard | ||
LVD | EN60950-1 | |
EMC | EN55022 |