Add to Cart
Dry Contact Outputs: The equipment must have dry contact outputs to report the basic alarms. You must have at least three dry contacts that report: No DC voltage at the input; No AC voltage at the input;
This is our popular one subrack inverter, we have more than 5000units sales every year.The performance of TP600-2U of inverter is at top of the market with peak efficiency up to 90% and small harmonics on DC side and it can be interfaced with RS232 and RS485.
Th unit have the ability to choose from which input the load will be fed. In the event that the load is fed through the AC input, the equipment ave a filter against electromagnetic interference, in order to improve the output waveform.
Here are the Features;
- 19”1U or 19”2U
- High Frequency standby design with
- Transfer time 5-8ms
- Working mode selectable (AC priority or DC priority)
- High Frequency design
- DC/AC isolation improving system security
- System parameters programmable
- Complete protection
- Thermal controlled fan
- RS232 or RS485 communication port and Dry point
- Voltage adjustable 230Vac (200-240) or 110Vac (100-120)
- Front panel connection version available
LED shows
Structure
Specifications
TP600D and TP600E (110VDC/220VDC models)
Model | TP605 | TP610 |
Electrical | ||
DC input | 110Vdc or 220Vdc | |
Dc input range | .-17% ~ +25% | |
AC Input | ||
AC input | 230Vac or 110Vac (-25%~+20%) | 230Vac (-25%~+20%) |
Frequency range | ±10% | |
Output power | 500va | 1kva |
Wave form | Pure sine wave | |
Power factor | 0.8 | |
Norminal output voltage | 230Vac or 110Vac | 230Vac |
Voltage variation | Max ± 2% | |
Output frequency | 50/60Hz ± 0.1Hz | |
Efficiency | Max 90% | |
THD | <3% liner load | |
<5% non-liner load | ||
Crest factor | .3:1 | |
Overload | 125% 60secs | |
110% 10mins | ||
Transfer time | 5-8ms | |
Dynamic response time | < 30ms | |
LVD | 91.5Vdc or 183Vdc | |
Display & Communication | ||
LED indicator | Working mode, Fault info | |
Communication Interface | RS232 and RS485 | |
4xDry contact | ||
Safety & Enviroment | ||
Operating Temp. | Full load, <-20℃> - 40℃ | |
Derating using, 40℃ - 60℃ | ||
Isolation | 2000Vrms | |
Mechanical | ||
Dimension (WxH) | 19"1U | |
Depth | 319mm | |
Weight | 4.0kgs/4.5kgs | |
Cooling | forced fan with thermal control | |
Enclosure | IP20 | |
Standard | ||
LVD | EN60950-1 | |
EMC | EN55022 |