TBB TP600 series inverter could achieve a compact size of maximized power density.
Combined with modern semiconductors and a patent pending control algorithm, TP600-1U inverter could achieve a compact size within the 19”1U height.
TP600-1U standalone inverter features an integrated utility bypass. With a dip switch, the inverter can be set into AC priority mode, of which power is always connected to the AC utility line and will switch to inverter power line when AC utility fails with transfer time less than 8ms.
LED or LCD version optional.
The performance of TP600-1U of inverter is at top of the market with peak efficiency up to 90% and small harmonics on DC side and it can be interfaced with RS232 and RS485.
Architecture: "Stand alone" rackable in 19 ".
- automatic bypass: the equipment must have 48VDC and 220VAC inputs so that in the event of an operational input failure, the equipment transfers load to the alternate input automatically, and the interruption or disturbance in the output must last less than or equal to 10ms.
Here are the Features;
- 19”1U or 19”2U
- High Frequency standby design with
- Transfer time 5-8ms
- Working mode selectable (AC priority or DC priority)
- High Frequency design
- DC/AC isolation improving system security
- System parameters programmable
- Complete protection
- Thermal controlled fan
- RS232 or RS485 communication port and Dry point
- Voltage adjustable 230Vac (200-240) or 110Vac (100-120)
- Front panel connection version available
LED shows
Specifications
TP600M and TP600S (24VDC/48VDC models)
Model | TP605 | TP610 |
Electrical | ||
DC input | 24Vdc or 48Vdc | 48Vdc |
Dc input range | .-17% ~ +25% | |
AC Input | ||
AC input | 230Vac or 110Vac (-25%~+20%) | 230Vac (-25%~+20%) |
Frequency range | ±10% | |
Output power | 500va | 1kva |
Wave form | Pure sine wave | |
Power factor | 0.8 | |
Norminal output voltage | 230Vac or 110Vac | 230Vac |
Voltage variation | Max ± 2% | |
Output frequency | 50/60Hz ± 0.1Hz | |
Efficiency | Max 88% | |
THD | <3% liner load | |
<5% non-liner load | ||
Crest factor | .3:1 | |
Overload | 125% 10secs | |
110% 10mins | ||
Transfer time | 5-8ms | |
Dynamic response time | < 30ms | |
LVD | 20Vdc or 40Vdc | 40Vdc |
Display & Communication | ||
LED indicator | Working mode, Fault info | |
Communication Interface | RS232 and RS485 | |
4xDry contact | ||
Safety & Enviroment | ||
Operating Temp. | Full load, <-20℃> - 40℃ | |
Derating using, 40℃ - 60℃ | ||
Isolation | 1500Vrms | |
Mechanical | ||
Dimension (WxH) | 19"1U | |
Depth | 319mm | |
Weight | 4.0kgs/4.5kgs | |
Cooling | forced fan with thermal control | |
Enclosure | IP20 | |
Standard | ||
LVD | EN60950-1 | |
EMC | EN55022 |
TP600D and TP600E (110VDC/220VDC models)
Model | TP605 | TP610 |
Electrical | ||
DC input | 110Vdc or 220Vdc | |
Dc input range | .-17% ~ +25% | |
AC Input | ||
AC input | 230Vac or 110Vac (-25%~+20%) | 230Vac (-25%~+20%) |
Frequency range | ±10% | |
Output power | 500va | 1kva |
Wave form | Pure sine wave | |
Power factor | 0.8 | |
Norminal output voltage | 230Vac or 110Vac | 230Vac |
Voltage variation | Max ± 2% | |
Output frequency | 50/60Hz ± 0.1Hz | |
Efficiency | Max 90% | |
THD | <3% liner load | |
<5% non-liner load | ||
Crest factor | .3:1 | |
Overload | 125% 60secs | |
110% 10mins | ||
Transfer time | 5-8ms | |
Dynamic response time | < 30ms | |
LVD | 91.5Vdc or 183Vdc | |
Display & Communication | ||
LED indicator | Working mode, Fault info | |
Communication Interface | RS232 and RS485 | |
4xDry contact | ||
Safety & Enviroment | ||
Operating Temp. | Full load, <-20℃> - 40℃ | |
Derating using, 40℃ - 60℃ | ||
Isolation | 2000Vrms | |
Mechanical | ||
Dimension (WxH) | 19"1U | |
Depth | 319mm | |
Weight | 4.0kgs/4.5kgs | |
Cooling | forced fan with thermal control | |
Enclosure | IP20 | |
Standard | ||
LVD | EN60950-1 | |
EMC | EN55022 |